AI WAC-4 Digital temperature controlled recirculating water chiller with built-in swivel casters, recommended for our IH series induction heaters (see models below). These chillers have built-in stainless steel tank, water pump and tubing for durability and rust-free operations. Water manifold included for immediate use.
Specifications
Model
WAC-4
Controller
Digital micro-chip controlled with LCD screen and fluid level display
Input power
415VAC 50/60Hz three-phase (3PH) 4.36kW
Nominal cooling capacity
8815 kcal per hour
Nominal cooling capacity is according to: Inlet chilled fluid temperature: 12°C Outlet chilled fluid temperature: 7°C Inlet cooling air temperature: 30°C Outlet cooling air temperature: 35°C
Compressor
Make: Danfoss (UL Listed) Power: 415VAC 50Hz 3-PH, C-SBN303H8A, thermally protected Refrigerant: R407C Number of compressors installed: one
Water pump
Make: CNP (CHLF(T)2-50) Power: 415VAC 50Hz 3-PH 550 watts 1.10A 2900 rpm IP55 Max liquid temperature: 70°C Pumping speed: 33L per minute Max pressure: H(max);45m, H(n): 20m
Reservoir capacity
30L
Recommended coolant
Distilled water
Cooling fan
Make: MAER (YWF74L34P4 -400) Power: 415VAC 50Hz 3-PH 432 watts 0.92A 1362rpm IP54 Number of fans installed: two Flow rate: 5,000 cu ft per hour
Temperature accuracy
+/- 2 °C
Water inlet & outlet on chiller
1”
Water manifold
Inlet: 1”, outlet: 1”
Unit/shipping weight
165 kg / 230 kg
Unit/shipping dimensions
1140 x560 x 1140 mm\ 1360*660*1440 (DxWxH)
Safety
Over current, compressor delay start, water pump over load, built-in fuse, over-voltage and under- voltage, abnormal operations, phase protection and
Working environment
Temperature range of chilled fluid: 5°C - 35°C. Temperature difference of chilled fluid between inlet and outlet: 3°C - 8°C. It is better to use the chiller while the ambient temperature is at or below 35°C
Recommended to use with these induction heaters (result may vary on different applications)
High frequency 10kW, 20kW, 30kW Mid frequency 25kW, 35kW Low frequency 25kW, 35kW